Carisma Fly is an innovative wall fan coil unit used in chilled water systems.

 

The use of an energy-efficient fan, together with a fully adjustable electric engine, ensures extremely low energy consumption (high energy rating) and quiet operation. High quality materials, such as steel casings, polyurethane foam insulation, polypropylene regenerating filters, copper and aluminium exchangers and a wide range of controllers, enable any assembly configuration. The innovative SabiaNet control system provides the user with comfort and ergonomic operation.

  • Wide range of individual and central control Options
  • 2-year warranty
  • DC fan engine with infinitely variable adjustment
  • Highest quality and durability of materials
  • Wired or wireless control
  • For wall mounting
Carisma Fly CVP-ECM Wall mounted type
Technical specifications

model

speed

V

Qch

Qg

Δpch

Δpg

Nel

Lw

Lp

 

 

m³/h

kW

kW

kPa

kPa

W

dB(A)

dB(A)

 

CVP-ECM 

 

min.

130

0,61

0,72

1,4

1,6

3

26

17

med.

290

1,57

1,78

7,7

7,5

9

46

37

max.

415

1,98

2,35

11,2

12,4

15

52

43

CVP-ECM 

min.

190

1,16

1,26

5,0

4,0

6

35

26

med.

290

1,57

1,78

7,7

7,5

9

46

37

max.

415

1,98

2,35

11,2

11,2

15

52

43

CVP-ECM

min.

260

1,46

1,63

6,9

6,4

7

40

31

med.

375

1,86

2,18

10,1

10,8

12

47

38

max.

510

2,24

2,74

14,1

16,3

22

55

46

CVP-ECM

min.

270

1,82

1,83

10,7

8,7

6

37

28

med.

420

2,52

2,63

19,0

16,6

11

45

36

max.

620

3,27

3,57

30,4

28,8

20

53

44

CVP-ECM

min.

375

2,33

2,40

16,5

14,1

9

43

34

med.

550

3,03

3,26

26,6

24,4

16

49

40

max.

770

3,72

4,20

38,7

38,7

30

57

48

 

V- Air flow [m3/h]

Qch- Cooling total emission [kW], Qg- Heating [kW]

Δpch- Dp Cooling [kPa], Δpg- Dp Heating [kPa]

Nel- electric power [W], power supply 230/1/50 V/Ph/Hz

Lp- Sound pressure [dB(A)], Lw- Sound power [dB(A)]

 